Section 6
SUPERVISOR II
BAUDRATE
• Sequence method - This parameter sets
the method used for optional sequencing.
The choices are DISABLED, REMOTE,
SLAVE, HOURS, COM ID#. See the
Sequencing & Protocol Manual (See
Recommended Spare Parts List) for details
about these modes.
SEQUENCE
• Drain interval - The time between actuation
of the drain valve.
DRN INTV
• Drain time - The amount of time that the
drain valve is actuated.
DRN TIM
• Last Communication Number - Used only
for sequencing, see Sequencing & Protocol
Manual for details.
LAST COM
• Lowest Allowable Pressure - Used only for
sequencing, see Sequencing & Protocol
Manual for details.
LOWEST
• Recovery Time - Used only for sequencing,
see Sequencing & Protocol Manual for
details.
RECOVER
• Rotate Time - Used only for sequencing -
units in HOURS, see Sequencing &
Protocol Manual for details.
50 HOURS
• Machine Capacity - Used only for sequenc-
ing
-
units
34
9600
HOURS
10 MIN
1 SEC
3
90 PSI
10 SEC
ROTATE
in
CFM
(M3/min),
Sequencing & Protocol Manual for details.
• Sequence Hours - Used only for sequenc-
ing, see Sequencing & Protocol Manual for
details.

6.7 OPERATING THE COMPRESSOR

Before operating the compressor the operating
parameters must be setup. See the previous sec-
tion on operating parameter setup.
MANUAL OPERATION MODE
In this mode the compressor will run indefinitely, as
long as temperatures and pressure remain within
the valid operating ranges, and the motor overload
or emergency stop contacts are not tripped.
Pressing the "
and put it in manual mode. If the compressor is
already running, but in automatic mode, pressing
"
" will switch operation to manual. Pressing
"
" while already running in manual mode will
cause the Supervisor to turn off the common fault
relay, if engaged, and clear any maintenance indi-
cators.
To stop the compressor, press "
pressor is already off when "
common fault relay will be turned off, if engaged,
and it will try to clear the alarm and maintenance
indicators. Regardless of what the compressor is
doing, pressing "
manual stop mode.
AUTOMATIC OPERATION MODE
In this mode the compressor will start if line pres-
sure (P2) is less than the LOAD parameter. It will
stop if the compressor runs unloaded for the num-
ber of minutes indicated by the UNLD TIM parame-
ter. To put the compressor in automatic mode press
"
". If P2 is already less than LOAD the com-
pressor will start immediately, otherwise the system
status will indicate STANDBY and the LED marked
AUTO will flash.
If the compressor is already running, but in contin-
uous mode, pressing "
see
to automatic. Pressing "
CAPACITY
100
SEQ HRS
1000
" will turn on the compressor
" If the com-
" is pressed, the
" puts the Supervisor in
" will switch operation
" while already run-