Chapter 4

Beep Codes

Beep Codes and Interpretation

Speaker beep code generation is supported on standby and when the system is powered up. The BMC may
emit the beep codes listed in the table below. The waveform below describes the timing and the sequence
of the Beep code 1-5-1-1---1 for power supply configuration failed to retain 3+1 redundancy.
BMC Beep Codes
Code
1-5-1-1
1-5-2-1
1-5-4-2
1-5-4-4
1-5-5-1
1-5-4-2
OR
1-5-4-4
300Ms
600Ms
Beep Code for 1-5-1-1 & 1 for Power Supply Configuration Failed to retain 3+1 redundancy
Description
FRB failure (processor failure)
No processors installed/detected
Power control fault. Power-good dropped out.
This beep code occurs during run time
PWRGD-BUF failure. System did not assert
power-good on power-up. Check installed
D2D configuration, verify processors seated,
processor power pods are connected, and
Legacy cable connector is secure with no bent
pins. This beep code ouccrs during system
power on.
CPU board interlock failure. Verify CPU board
inserted fully.
1
Power Supply Configuration Failed to retain
3+1 redundancy (1 Redundant)
2-1
Processor1 Power Good failed due to power
pod failure or not connected to 48V
2-2
Processor2 Power Good failed due to power
pod failure or not connected to 48V
2-3
Processor3 Power Good failed due to power
pod failure or not connected to 48V
2-4
Processor4 Power Good failed due to power
pod failure or not connected to 48V
3-1
Upper Memory board power good failed.
3-1
Lower Memory board power good failed.
4
12V D2D Power Good failure.
5-1
I/O 5V A D2D Power Good failure.
5-2
I/O 5V B D2D Power Good failure.
6
PROC 3.3V D2D Power Good failure.
7-1
I/O 3.3V A D2D Power Good failure.
7-2
I/O 3.3V B D2D Power Good failure.
8-1
1.8V D2D Power Good failure (processor
board only).
300Ms
600Ms
600Ms
3Sec
Diagnostics
45