REVERSING ELECTRICAL CONNECTION & THERMOSTAT
4. Remove 7/8" plug from hole opposite j-box location.
Drill 2 @ 3/16" Ø holes in the jacket. NOTE: Dim-
ples/marks are provided in the sheet metal for correct
drilling location.
5. Move the junction box to the opposite side of the cabi-
net. Install using the two screws removed in step 3
above. Note that all screws penetrating the junction
box must be blunt – no sharp tipped screws can be
used.
6. Replace the plug from the opposite of the furnace (the
new j-box location) to the old j-box location and install
qty=2 1/4" plugs from parts bag in empty screw holes
in old location of j-box into the mounting screw holes
in the old junction box location.
7. Using fingers, squeeze the retaining arms on the door
switch and gently pry the door switch from it's opening
as shown in Figure 44.
8. Install the door switch in the same opening on the op-
posite of the furnace and reconnect the electrical con-
nectors (removed in Step 2) to the door switch. To
mate wire terminal to ¼" spade terminal, grasp the ter-
minal from the housing with fingers and push straight
against ¼" spade terminal. This low insertion force
flag terminal will deliver an audible click when en-
gaged. Failure to engage will cause defective contact.
THERMOSTAT
The room thermostat must be compatible with the furnace.
See manufacturer's thermostat spec sheet for compatibil-
ity concerns. Generally, all thermostats that are not of the
"current robbing" ("current robbing" thermostats require the
addition of an isolation relay. See Figure 45) types are
compatible with the integrated furnace control. The low
voltage wiring should be sized as shown.

ELECTRICAL WIRING

NOTE: Do not use 24 volt control wiring smaller than No.
18 AWG.
Install the room thermostat in accordance with the instruc-
tion sheet packed in the box with the thermostat. Run the
thermostat lead wires inside the blower compartment and
connect to low voltage terminals as shown on the wiring
diagram. Never install the thermostat on an outside wall or
where it will be influenced by drafts, concealed hot or cold
water pipes or ducts, lighting fixtures, radiation from fire-
place, sun rays, lamps, televisions, radios or air streams
from registers.
FIGURE 45
ISOLATION RELAY
ST-A1194-75-00
ST-A1194-75-00
59