9 Inspection and maintenance
9.4

Carrying out electronics self-tests

Menu → Installer level → Test programs → Electronics
self-test
You can use the electronics self-test to check the PCB in
advance.
9.5
Removing the gas-air mixture unit
Note
The gas-air mixture unit consists of four main
components:
– Speed-regulated fan,
– Air intake pipe,
– Gas valve,
– Burner
1.
Switch off the product using the on/off button.
2.
Disconnect the product from the power mains.
3.
Close the gas isolator cock.
4.
Remove the front casing. (→ Page 10)
5.
Remove the upper casing. (→ Page 10)
Conditions: Applies for 80 kW
2
Undo the clip (1) on the air intake pipe (2). and remove
the air intake pipe from the intake nozzle.
Undo the four screws on the flange connection (3) to the
gas valve.
28
Conditions: Applies for 100 kW and 120 kW
Undo the four screws on the flange connection (3) to the
gas valve.
6.
Move the gas pipe (4) to the side.
1
3
4
Installation and maintenance instructions ecoTEC plus 0020134823_04
3
4