5-8. COMPRESSOR CONTROL
1. OPERATION FREQUENCY RANGE
The operation frequency of the compressor is different based on the operation mode as
shown in Table 9.
(Table 9 : Compressor Operation Frequency Range)
AU*A12LALN
AU*A14LALN
AU*A18LALN
AU*A24LALN
AU*A36LATN
AU*A45LATN
2. OPERATION FREQUENCY CONTROL AT START UP
2-1. For AU*A12/ 14/ 18/ 24LALN
The compressor frequency soon after the start-up is controlled as shown in Figure 10.
(Fig.10 : Compressor Control at Start-up)
85Hz
59Hz
40Hz
2-2. For AU*A36/ 45LATN
The compressor frequency soon after the start-up is controlled as shown in Figure 11.
(Fig.11 : Compressor Control at Start-up)
70Hz
54Hz
43Hz
28Hz
Cooling
Min
Max
18Hz
113Hz
18Hz
113Hz
18Hz
113Hz
18Hz
113Hz
18Hz
77Hz
18Hz
77Hz
90sec
180sec
90sec
180sec
05-10
Heating
Min
Max
18Hz
120Hz
18Hz
120Hz
18Hz
120Hz
18Hz
120Hz
18Hz
90Hz
18Hz
90Hz
270sec
270sec
Dry
34Hz
34Hz
34Hz
34Hz
31Hz
31Hz
360sec