9. Enter button to save choice
10. Left button (3x) to home screen.
System Enable – to enable heating / cooling from home screen, press:
1. Right button to access the Main Menu Screen
2. Down button through entries to highlight System
3. Enter button to select System and enter System Screen
4. Enter button again to highlight current System Enable choice
5. Up/Down buttons to choose from available System Enable options
Auto: System is in "Auto-Changeover" mode. HVAC system will cycle heating and cooling automatically to
stay within preset heating and cooling setpoints.
Heating: System is in "Heating-Only" mode. HVAC system will cycle heating in reference to Heating
Setpoint only. Unit will not activate cooling sequence.
Cooling: System is in "Cooling-Only" mode. HVAC system will cycle cooling in reference to Cooling Setpoint
only. Unit will not activate heating sequence.
Emer HT: HP mode only.
Off: HVAC system is inactive.
6. Enter button to select/save appropriate mode selection
7. Left button (2x) to navigate back to home page.
Temperature Setpoints – to access temperature setpoints from the home screen, press:
1. Right button to access the Main Menu Screen
2. Down button through entries to highlight Setpoints
3. Enter button to select Setpoints and enter Setpoints Screen
4. Enter button to select Cool Setpt
5. Up/Down buttons to enter appropriate cooling setpoint
6. Enter button to save new Cool Setpt
7. Down button to highlight Heat Setpt
8. Enter button to select Heat Setpt
9. Up/Down buttons to enter appropriate heating setpoint
10. Enter button to save new Heat Setpt
11. *REPEAT STEPS IN LIKE FASHION FOR COOL SETBACK & HEAT SETBACK TEMPERATURES, DEHUM SETPOINT & SPAN,
& FOR C0
SETPOINT IN PARTS PER MILLION & C0
2
12. Left button (2x) to navigate back to home page
3
NOTE
: The controller will not allow heating/cooling setpoints to contradict one another, or to be within a degree of
conflicting operation.
4
NOTE
: Any system start-up with indoor ambient temperatures lower than 56° F., or above 86° F. will experience an
internal Low-Temperature or High-Temperature alarm. This will not affect normal operation, and can be cleared easily.
Terminal Descriptors – Optional Inputs
D SC
A
W2 W1/E SC
Remote Occupancy Sensor
(TBD)
8301-062 Indoor Remote
Air Temperature Sensor
NOTE: Use twisted shielded pair for optional outdoor and indoor air sensors. Connect shield (drain) to 24V common.
2100-566D
Page 6 of 20
3
4
SPAN OF CONTROL IN PARTS PER MILLION (IF AVAILABLE).*
2
Y2
Y1 YO
SC
O/B
G
BACnet Commercial
Controls Platform
A+ B-
IN9 ROS GND REM
TM
CompleteStat
GND L COM 24V
OAT LAT
8301-014 Leaving Air
Temperature Sensor
8301-061 Outdoor Air
Temperature Sensor