Basic Operation: Home, Main Menu, and Override Screens
Navigate the menus & change settings by pressing a combination of various arrow buttons/the Enter button. Push the:
Enter button to select and/or exit value editing
Up or Down button to move among entries
Right or Left button to move among value fields
Left button to return to the home screen
2

NOTE

: Although cooling/heating setpoints can be accessed by simply pressing the arrow keys during normal operation,
any changes made in this fashion will be for a specific length-of-time as an "override" feature only. This temperature
change will not be permanent. See the Temperature Setpoints for further information.
Quick Start Programming: System Selection, System Enable, Aux. Heat, and Temperature Setpoints.
System Selection – to select A/C or HP, stages of heating and cooling, and with/without economizer, press:
1. Right button to access the Main Menu screen
2. Down button through entries to highlight Advanced
3. Enter button to select Advanced and enter Advanced Screen
4. Enter button again to select/enter Applications Screen
5. Controller will ask for Admin Level Password
Factory Default Admin Level Password: BARD
Press Enter
6. Enter button to choose Degrees Scale (IF NECESSARY)
1
*NOTE
: On changing temperature scale, the APP category must be set to
"NOT CONFIGURED" before the controller will allow you to change scale
7. Up/Down buttons to choose °Fahrenheit or °Celsius
8. Enter button to save selection of scale. See Note A.
9. Down button to highlight App
10. Enter button to highlight current selection
11. Up/Down buttons to choose from available System types:
A/C
HP
12. Enter button to select/save appropriate model
13. Down button to highlight Opt
14. Enter button to highlight current selection
15. Up/Down buttons to choose from available System Stages:
AC
1H/1C
2H/2C
1H/2C
2H/1C
16. Enter button to select/save appropriate model stage
17. Down button to highlight Additional Setup
18. Enter button to select/enter Additional Setup Screen
19. Down button to highlight Damper, press Enter button to select
2100-566D
Page 4 of 20
2
1
HP
1 Stage
2 Stage
Note A. The change from "F" to "C"
will not take effect on the Home Screen
until the 24VAC power is cycled off and
back on.