User Settings
The UPS has the following typical settings that are user configurable. Note that some of the
settings become effective at the next start-up of the UPS. User settings can configured via the
front panel. Select: SETTINGS -> USER SETTINGS.
Description
General:
Display contrast adjustment
Display language
Date & time
Audible alarms
Normal screen in display
User settings password
Nominal values:
Nominal output voltage (L-N)
Nominal output frequency
Rectifier phase current limit
Communication and connectivity:
Disable control commands
Communication speed
Std. relay output function
Signal input #1-2 function
Hardware remote off delay for hardware
Remote off with restart function.
XSlot relay output 1-4 function
XSlot input signal (long break via Rx)
XSlot shutdown signal activation delay before
the signal is accepted.
Bypass and syncronisation:
Usage of bypass
Require synch at transfer on bypass
Transfer on bypass on overload
Synchronization enable
Bypass voltage deviation high limit
Bypass voltage deviation low limit
Synchronization window
Frequency slew rate (not in parallel mode)
30
Available settings
+ / -
[English], [Spanish], [French], [German]
[xxxx-xx-xx]
[Normal], [Disabled]
[logo], [mimic]
[Not required], [Set]
[220], [230], [240]
[50 Hz], [60 Hz]
Step: 1 A
[Enabled], [Disabled]
[1200], [2400], [9600], [19200]
[UPS ON/OK], [Custom], [Battery low],
[System on bypass], [System on battery]
[Empty], [see Signal inputs]
Step: 1 sec.
[Nothing], [see Signal inputs]
Step: 1 sec.
[Enabled], [Disabled]
[Required], [Not Required]
[Immediately], [after delay]
[Enabled], [Disabled]
+1% ... +20%, step: 1%
-1% ... -20%, step: 1%
0.5 ... 3.0 Hz, step: 0.1 Hz
0.1 ... 3.0 Hz/s, step 0.1 Hz/s
UPS 20-30 kVA, 230 V 0/60 Hz output
User's Guide
Default setting
Moderate
English (British)
0001-01-01
Normal
Product name
Not required
230 Volts
50 Hz
56 A
Disabled
19200 bps.
UPS ON/OK
Empty
120 sec
XSlot defaults:
#1: on battery
#2: battery low
#3: UPS on/ok
#4: on bypass
Nothing
5 sec
Enabled
Not required
Immediately
Enabled
+10%
-15%
±2.0 Hz
0.2 Hz/s
1026743
Revision B