Ac Input; Dc Circuit; Ac Output - Eaton Powerware 9155 UPS20-30kVA User Manual

230v 50/60 hz output (3-phase input/1-phase output)
Table of Contents

Advertisement

AC input
Powerware 9155
Rectifier input
Bypass input
Voltage (L-N)
Frequency
Power factor
Input distortion
Rated input current
DC circuit
Powerware 9155
Management
Nominal voltage
Battery qty
Float voltage
Battery type
Cut off voltage
Battery charging
AC output
Powerware 9155
Active power
Number of phases
Frequency
Voltage (L-N)
Short circuit capability
Overload capability
Overload capability
(mains available)
1026743
Revision B
20 kVA
3 phases + N
1 phase + N
192 to 276 Volts without using battery
< 5% THD(I)
29 A
20 kVA
Advanced Battery Management
VRLA 12 Volts
6 A (default), user selectable
20 kVA
18 kW
1-phase + N
50 Hz or 60 Hz, user selectable
220, 230 or 240 Volts, user selectable
300 A < 300 ms
10 min > 100 – 110% load
1 min > 110 – 125% load
5 sec > 125 – 150% load
300 ms > 150% load
60 min > 100 – 110% load
10 min > 110 – 125% load
1 min > 125 – 150% load
UPS 20-30 kVA, 230 V 0/60 Hz output
User's Guide
30 kVA
45 to 65 Hz
0.99
43 A
30 kVA
432 Volts
36 / string
2.30 VPC
1.75 VPC
30 kVA
27 kW
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9155 20 kvaPowerware 9155 30 kva

Table of Contents