The Fixed Master Sync Control can be installed in your facility up to a maximum of
500 feet from the single module Powerware 9315 UPS or Powerware Hot
Sync---Capacity system. When the Fixed Master Sync Control has been moved to
its installed location, unpacked, and inspected, it is ready for installation. This
section discusses typical installation of the Powerware Fixed Master Sync Control.
Refer to the following while installing the Powerware Fixed Master Sync Control:
Figure 164201325---1 of Appendix A of this manual for mounting hole
dimensions, conduit entrance locations, and equipment grounding terminal
location.
Detailed control wiring information is provided in Tables 1, 2, and 3 of
Appendix A of this manual.
OEM Installation manual for interconnection to master source (provided by
others)
Install the Powerware Fixed Master Sync Control panel to the selected mounting
location.
NOTE: The Fixed Master Sync Control requires that both the Powerware (Slave)
system and the Master System voltage and frequency be the same. Verify the
voltage and frequency of both systems with the nameplate rating of the Fixed
Master Sync Control.
Complete all control wiring interconnections using Tables 1, 2, and 3 of Appendix A
for wiring requirements. Figures 2 through 5 show the typical location of the TB1
and TB6 interconnect terminal blocks, within a single module Powerware 9315
UPS. Figure 6 shows customer TB2 connections for 750kVA unit. Figures 7 and 8
show the typical location of the System Bypass Module (SBM) Customer Interface
Panel for the Powerware Hot Sync---Capacity. Figure 9 shows the TB3, TB4, TB6
and TB7 interconnect terminal blocks located on the SBM Customer Interface
Panel. Figure 10 shows typical control wiring and power wiring terminations of the
Powerware Fixed Master Sync Control. Also, refer to the Powerware 9315 UPS
Installation manual provided with the single module Powerware 9315 UPS system
or the Powerware 9315 Parallel Capacity/Redundant System (Hot Sync---Capacity)
Installation manual provided with the SBM for location of UPS module and SBM
cabinet wiring terminations.
NOTE: Material and labor for external wiring are to be provided by designated
personnel.
Powerware 9315 Fixed Master Sync Control
164201325 Rev. A 060203
Fixed Master Sync Control
Shut down all sources of power to the single module Powerware
9315 UPS or Powerware Hot Sync-- Capacity system before
connecting the control wiring to the Fixed Master Sync Control
enclosure and UPS system or System Bypass Module (SBM).
Hazardous voltages exist inside the UPS modules and in the
Fixed Master Sync Control enclosure. Check all terminal
conductors with a known serviceable voltmeter before connecting
the wiring. Installation should only be performed by qualified
Installing the Powerware
WARNING
personnel.