Emerson Rosemount OCX8800 Instruction Manual page 157

Oxygen and combustibles transmitter, hazardous location probe with integral electronics
Hide thumbs Also See for Rosemount OCX8800:
Table of Contents

Advertisement

Instruction Manual
IM-106-880C, OI
Index
Parameter
Number Units
CONTROL_OPTS
13
DV_HI_ALM
64
DV_HI_LIM
57
DV_HI_PRI
56
DV_LO_ALM
65
DV_LO_LIM
59
DV_LO_PRI
58
ERROR
67
FF_ENABLE
70
FF_GAIN
42
FF_SCALE
41
FF_VAL
40
GAIN
23
GRANT_DENY
12
HI_ALM
61
HI_HI_ALM
60
HI_HI-LIM
49
HI_HI_PRI
48
HI_LIM
51
HI_PRI
50
IN
15
LO_ALM
62
LO_LIM
53
LO_LO_ALM
63
LO_LO_LIM
55
LO_LO_PRI
54
Proportional/ Integral/Derivative (PID) Function
Block
Description
None
Allows you to specify control strategy options. The supported control
options for the PID block are Track enable, Track in Manual, SP-PV Track
in Man, SP-PV Track in LO or IMAN, Use PV for BKCAL OUT, and Direct
Acting.
None
The DV HI alarm data, which includes a value of the alarm, a timestamp
of occurrence, and the state of the alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the deviation high alarm
condition.
None
The priority of the deviation high alarm.
None
The DV LO alarm data, which includes a value of the alarm, a timestamp
of occurrence, and the state of the alarm.
EU of PV_SCALE
The setting for the alarm limit use to detect the deviation low alarm
condition.
None
The priority of the deviation low alarm.
EU of PV_SCALE
The error (SP-PV) used to determine the control action.
None
Enables the use of feedforward calculations.
None
The feedforward gain value. FF_VAL is multiplied by FF_GAIN before it
is added to the calculated control output.
None
The high and low scale values, engineering units code, and number of
digits to the right of the decimal point associated with the feedforward
value (FF_VAL).
EU of FF_SCALE
The feedforward control input value and status.
None
The proportional gain value. This value cannot = 0.
None
Options for controlling access of host computers and local control pan-
els to operating, tuning, and alarm parameters of the block. Not used
by the device.
None
The HI alarm data, which includes a value of the alarm, a timestamp of
occurrence, and the state of the alarm.
None
The HI HI alarm data, which includes a value of the alarm, a timestamp
of occurrence, and the state of the alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the HI HI alarm condition.
None
The priority of the HI HI Alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the HI alarm condition.
None
The priority of the HI alarm.
EU of PV_SCALE
The connection for the PV input from another block.
None
The LO alarm data, which includes a value of the alarm, a timestamp of
occurrence, and the state of the alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the LO alarm condition.
None
The LO LO alarm data, which includes a value of the alarm, a timestamp
of occurrence, and the state of the alarm.
EU of PV_SCALE
The setting for the alarm limit used to detect the LO LO alarm
condition.
None
The priority of the LO LO alarm.
Section 7: Foundation
Fieldbus
April 2017
13
1