3.15.4 Bias and gain of frequency setting voltage (current)
(Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905))
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting
signal (0 to 5V, 0 to 10V or 4 to 20mADC).
Set Pr. 73 and Pr. 267 to switch between 0 to 5VDC, 0 to 10VDC and 0 to 20mADC. (Refer to page 125)
Parameter
Number
Terminal 2 frequency setting gain
125
frequency
Terminal 4 frequency setting gain
126
frequency
Analog input display unit
241
*1, 3
switchover
Terminal 2 frequency setting bias
C2(902)
*1, 2
frequency
Terminal 2 frequency setting bias
C3(902)
*1, 2
C4(903)
Terminal 2 frequency setting gain
*1, 2
Terminal 4 frequency setting bias
C5(904)
*1, 2
frequency
C6(904)
Terminal 4 frequency setting bias
*1, 2
C7(905)
Terminal 4 frequency setting gain
*1, 2
*1
The parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 140.)
*2
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04).
*3
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77
Parameter write selection.
Name
Initial Value
50Hz
50Hz
0Hz
100%
0Hz
20%
100%
Frequency setting by analog input (terminal 1, 2, 4)
Setting
Range
Set the frequency of terminal 2
0 to 400Hz
input gain (maximum).
Set the frequency of terminal 4
0 to 400Hz
input gain (maximum).
Displayed
0
in %
0
Displayed
1
in V/mA
Set the frequency on the bias side
0 to 400Hz
of terminal 2 input.
Set the converted % of the bias
0%
0 to 300%
side voltage (current) of terminal 2
input.
Set the converted % of the gain
0 to 300%
side voltage of terminal 2 input.
Set the frequency on the bias side
0 to 400Hz
of terminal 4 input.
Set the converted % of the bias
0 to 300%
side current (voltage) of terminal 4
input.
Set the converted % of the gain
0 to 300%
side current (voltage) of terminal 4
input.
Pr. 124
page 161
Pr. 127
page 184
Pr. 240
page 124
Description
Pr. 242
page 127
Select the unit of
analog input display.