Mitsubishi Electric F700 Instruction Manual page 207

Hide thumbs Also See for F700:
Table of Contents

Advertisement

Special operation and frequency setting
· Alternative system (Pr. 579 = "1"), direct system (Pr. 579 = "2"), alternative-direct system (Pr. 579 = "3")
Power
supply
Forward rotation
Reverse rotation
Advanced PID
control selection
PID forward
-reverse
action switching
Setting
potentiometer
(Set point setting)
Deviation signal
*1
When driving three or more motors, use the plug-in option (FR-A7AR).
*2
Always provide mechanical interlocks for the MC.
(3) I/O signals
· Turn the X14 signal on when performing advanced PID control. Set "14" in Pr. 186 to Pr. 189 (input terminal
function selection) to assign a function to the X14 signal.
· PID control depends on the Pr. 127 to Pr. 134 settings. (Refer to page 184)
· Use Pr.190 to Pr.196 (output terminal function selection) or relay output option (FR-A7AR) to assign functions of motor
control signal to Pr.320 to Pr.322 (RA1, RA2, RA3 output selection). (Only positive logic is available for output terminals.
Output Terminal Function
Selection Setting
Signal
Positive
logic
SLEEP
70
RO1
71
RO2
72
RO3
73
RO4
74
RIO1
75
RIO2
76
RIO3
77
RIO4
78
SE
200
Inverter
RST
UVW
STF
RI01
FU
STR
R01
X14
OL
RT
RI02
X64
IPF
JOG
R02
PC
SU
RI03
10
RUN
2
SE
FR-A7AR
5
(Option)
*1
R03
1
1A
4
1C
RI04
2A
2C
R04
3A
3C
(Process value) 4 to 20mA
0
24V
Power
supply
Negative
logic
170
During PID output interruption
*1
Commercial-power supply side motor 1 connection
*2
Commercial-power supply side motor 2 connection
*2
Commercial-power supply side motor 3 connection
*2
Commercial-power supply side motor 4 connection
*2
Inverter side motor 1 connection
*2
Inverter side motor 2 connection
*2
Inverter side motor 3 connection
*2
Inverter side motor 4 connection
*2
Output terminal common
*2
MC
RI01
MC
RI01
R01
R01
RI02
RI02
R02
R02
RI03
RI03
R03
DC24V
MC
R03
RI04
RI04
R04
R04
Source logic
When Pr. 183 = 14, Pr. 185 = 64
Pr. 194 = 75, Pr. 193 = 71, Pr. 192 = 76
Pr. 191 = 72, Pr. 190 = 77, Pr. 320 = 73
Pr. 321 = 78, Pr. 322 = 74
Function
Example
Distributed water
*2
M1
PUMP4
M2
PUMP3
M3
PUMP2
M4
PUMP1
For 2-wire
type
Supplied water
-
*1
This value can not be set in Pr. 320
to Pr. 322 (RA1, RA2, RA3 output
selection), parameters for relay
output option (FR-A7AR).
*2
Negative logic can not be set.
Detector
+

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents