Bias And Gain Of Frequency Setting Voltage (Current) [Pr. 125, Pr. 126, Pr. 241, C2 (Pr. 902) To C7 (Pr. 905)] - Mitsubishi Electric FR-E700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-E700:
Table of Contents

Advertisement

Frequency setting by analog input (terminal 2, 4)
6.16.3
Bias and gain of frequency setting voltage (current) [Pr. 125, Pr. 126,
Pr. 241, C2 (Pr. 902) to C7 (Pr. 905)]
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency
setting signal (0 to 5V, 0 to 10V or 0/4 to 20mA DC).
These parameters can be used to configure the inverter precisely for set point signals that either
exceed or do not quite reach 5V or 10V or 20mA. These settings can also be used to configure
inverse control (i.e. high output frequency at minimum set point signal, minimum output
frequency at maximum set point signal).
Pr. No. Name
Terminal 2 frequency setting
125
gain frequency
Terminal 4 frequency setting
126
gain frequency
Analog input display unit
241
switchover
C2
Terminal 2 frequency setting
(902)
bias frequency
C3
Terminal 2 frequency setting
(902)
bias
C4
Terminal 2 frequency setting
(903)
gain
C5
Terminal 4 frequency setting
(904)
bias frequency
C6
Terminal 4 frequency setting
(904)
bias
C7
Terminal 4 frequency setting
(905)
gain
The above parameters can be set when Pr. 160 "User group read selection" = 0.
The parameter number in parentheses is the one for use with the operation panel (PA02)
for the FR-E500 series or parameter unit (FR-PU04/FR-PU07).
The above parameter allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
6 - 180
Initial
Setting
Description
Value
Range
Set the frequency of terminal 2
50Hz
0–400Hz
input gain (maximum).
Set the frequency of terminal 4
50Hz
0–400Hz
input gain (maximum).
0
Displayed in %
0
Displayed in
1
V/mA
Set the frequency on the bias side
0Hz
0–400Hz
of terminal 2 input.
Set the converted % of the bias
0%
0–300%
side voltage (current) of terminal
2 input.
Set the converted % of the gain
100%
0–300%
side voltage of terminal 2 input.)
Set the frequency on the bias side
0Hz
0–400Hz
of terminal 4 input.
Set the converted % of the bias
20%
0–300%
side current (voltage) of terminal
4 input.
Set the converted % of the gain
100%
0–300%
side current (voltage) of terminal
4 input.
Parameters referred to
20
Acceleration/
deceleration
reference
frequency
73
Analog input
selection
Select the unit of
267
Terminal 4 input
analog input
selection
display.
79
Operation mode
selection
Parameter
Refer to
Section
6.7.1
6.16.1
6.16.1
6.18.1