IDLE STATE
THERMOSTAT
CALLS FOR HEAT
4,
F
OIL PRIMARY
CONTROL
SAFETYCHECKFORFLAME(5SEC.)
I
l
NO FLAME
BURNER
MOTOR
& IGNITOR
START
I
10 SEC.
SAFETY
CHECK
FOR FLAME
(5 SEC.)
I
NO FLAME
REMAINS IN IDLE STATE
FLAME
1
SEQUENCE of
OPERATION
SOLENOID VALVE OPENS
TRIAL FOR IGNITION
I
4,
BURNER FLAME MONITORED
FLAME
CARRYOVER STATE
•
Provides continuous spark
•
LED diagnostic light ON
•
Start Carryover Timer
FLAME
FLAME
NO FLAME
FLAME LOST
,L
I
OCKOUT STATE
l
OIL PRIMARY CONTROL:
Shuts off burner motor
Shuts off igniter
Shuts off Solenoid Valve
Fast Flashes LED Diagnostic
Light
CARRYOVER TIMER EXPIRES
FLAME
RUN STATE
•
Igniter turns off.
FLAME LOST
I
FLAME LOST
THERMOSTAT
SATISFIED
4,
OIL PRIMARY CONTROL
SHUTS OFF:
•
Burner Motor
•
Solenoid Valve
30 SEC.
I
SAFETY CHECK FOR FLAME (5 SEC.) I
I
NO FLAME
i
RETURNS TO IDLE STATE
FLAME
RECYCLE TIMER STARTS
OIL PRIMARY CONTROL:
Shuts off Solenoid Valve
Shuts off Igniter
Shuts off Burner Motor
Slow Flashes LED
diagnostic light
RECYCLE TIMER EXPIRES
(60 SECONDS
22