Nordyne O4HD-091A-14-FA-DV Installation, Operation And Maintenance Manual page 26

Oil fired warm air furnaces
Table of Contents

Advertisement

Table C-3: Oil Primary Control Troubleshooting
continued from previous page
Procedure
Status
Indicator light turns off.
4. Shield cad cell from external
light.
5. Jumper thermostat (T -T)
terminals on oil primary control
IMPORTANT
First remove one thermostat
lead wire.
Indicator light stays on.
Burner starts.
Burner does not start.
Corrective
Action
Eliminate external light source or permanently shield cad cell.
Replace cad celt with new cad cell and recheck.
If indicator light does not turn off, remove cad cell lead wires
from oil primary control and recheck.
If indicator light turns off, replace cad cell bracket assembly.
If indicator light does not turn off, replace controller.
Trouble in thermostat or limit circuit. Check thermostat or limit
wiring connections.
Disconnect the line voltage power and open line switch.
Check all wiring connections.
Tighten any loose connections and recheck.
If burner does not start, replace oil primary control
Condition: Burner starts then locks out on safety with indicator light flashing at 1 Hz rate (1/2second on, 1/2 second
off)
6. Reset oil primary control by
pushing in and releasing red
reset button.
7. Listen for spark after burner
turns on (after 2 second delay).
8. Check indicator light after
flame is established, but before
oil primary control locks out.
9. Check cad cell sighting for
view of flame.
Disconnect line voltage power
and open line switch.
Unplug cad celt and clean cad
celt face with soft clothe. Check
sighting for clear view of flame.
Replace cad celt in socket.
Reconnect line voltage power
and close line switch.
Start burner.
Indicator light stops flashing.
Indicator light continues to
flash at 1 Hz rate.
Ignition is off
Ignition is on.
Ignition is on but no oil is
being sprayed into the
combustion chamber.
Indicator light is on until the
control locks out and starts
flashing during lockout.
Indicator light stays off.
Burner locks out.
Burner keeps running.
Go to Step 7.
Verify that the control is not in restricted mode. (See notes at
end of this table.). If not in restricted mode, replace oil
primary control
Spark igniter could be defective. Check for line voltage at
igniter terminals. If line voltage is present, replace oil primary
control.
Go to Step 8.
Wait for "Valve ON" delay to complete. Check oil supply, and
oil line valve. Check for filter blockage or seized oil pump.
Replace oil primary control
Go to step 9.
Go to step 10.
System is OK.
26