PROFINET interface X1 with 2-port switch (X1 P1 R and X1 P2 R)
The pin assignment of the ports depends on the setting of the port option "Activate
autonegotiation".
● Port P1 X1 R: When autonegotiation is deactivated, the RJ45 socket is allocated as data
terminal equipment MDI (normal pin assignment).
● Port P2 X1 R: When autonegotiation is deactivated, the RJ45 socket is allocated as a
switch MDI-X (crossed pin assignment).
● The following applies to both ports: When autonegotiation is activated, autocrossing is in
effect and the RJ45 socket is allocated either as data terminal equipment MDI or a switch
MDI-X.
The figure below shows the location of the PROFINET interface X1 and the connection
socket for the 24 V DC supply voltage.
Figure 3-1
Note
You need a screwdriver (max. blade width 2.5 mm) to remove the PROFINET plug.
Note
IM 155-5 PN ST interface module (6ES7155-5AA00-0AB0)
For the IM 155-5 PN ST with order number 6ES7155-5AA00-0AB0, note that the ports of the
PROFINET interface X1 are offset by 90°.
Interface module IM 155-5 PN ST (6ES7155-5AA01-0AB0)
Manual, 11/2017, A5E03612323-AC
Port P1 X1 R (front)
Port P2 X1 R (rear)
Connection socket 24 V DC supply voltage
Location of the PROFINET ports and the 24 V DC connection socket (view from below)
Wiring
3.1 Terminal assignment
21