3 Specifications and Application Procedures
Item
Power supply
voltage
NX Unit power
supply capacity
NX Unit power
Unit power
supply efficiency
supply
Isolation method
Current capacity
of power supply
terminals
Power supply
voltage
Maximum I/O
I/O power
power supply cur-
supply
rent
Current capacity
of power supply
terminals
NX Unit power consumption
Current consumption from I/O
power supply
Dielectric strength
Insulation resistance
External connection terminals
Dimensions
Weight
3 - 4
24 VDC (20.4 to 28.8 VDC)
10 W max.
Refer to Installation orientation and restrictions for details.
70%
No isolation between NX Unit power supply and Unit power supply termi-
nals
4 A max.
5 to 24 VDC (4.5 to 28.8 VDC)
10 A
Refer to Installation orientation and restrictions for details.
10 A max.
1.60 W max.
10 mA max. (for 24 VDC)
510 VAC for 1 min, leakage current: 5 mA max. (between isolated circuits)
100 VDC, 20 MΩ min. (between isolated circuits)
Communications Connector
For EtherNet/IP communications.
• RJ45 × 2 (shielded)
Screwless Clamping Terminal Block
For Unit power supply, I/O power supply, and grounding. Removable.
Peripheral USB Port
To connect Support Software
• Physical layer: USB 2.0-compliant, B-type connector
• Transmission distance: 5 m max.
46 × 100 × 71 mm (W×H×D)
150 g max.
NX-series EtherNet/IP Coupler Unit User's Manual (W536)
Specification
*2