Operation Details - LG LS-H0560CL Service Manual

Table of Contents

Advertisement

Operation Details

(1) The function of main control
1. Time Delay Safety Control
• 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle.
(Protection of compressor)
• 5sec.; The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical
louver and wind.
2. Airflow Direction Control
• This function is to swing the vertical louver up and down automatically and to set it at a fixed position.
• The procedure is as the following.
1st ; Press the ON/OFF Button to operate the unit.
2nd ; Press the Airflow Direction Control Button to swing the vertical louver up and down automatically.
3nd ; Repress the Airflow Direction Control Button to set the vertical louver at a fixed position.
3. Cooling Mode Operation
• When selecting the Cooling(
remote controller and the operation diagram is shown below.
INTAKE AIR TEMP.
SETTING TEMP. +0.5°C
(Compressor ON)
SETTING TEMP. -0.5°C
(Compressor OFF)
INDOOR FAN SPEED
COMPRESSOR
) Mode Operation, the unit will operate according to the setting by the
More than
3 minutes
Selecting
Low
fan speed
ON
OFF
108°
Selecting
fan speed
ON
—9—
More than
3 minutes
Selecting
Low
fan speed
OFF
ON