Operation Details - LG LP-K2060CL Service Manual

Table of Contents

Advertisement

Operation Details

(1) The function of main control
1. Time Delay Safety Control
3min
The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
3sec
The indoor fan is ceased for 3 seconds to prevent relay noise.
(Protection of fan relay and micro chip)
30sec
The 4-way valve is ceased for 30 sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode.
2. Airflow Direction Control
This function is to swing the louver left and right automatically and to set it at the desired position.
The procedure is as the following.
1st : Press the ON/OFF Button to operate the product.
2nd : Press the Airflow Direction Control Button to swing the louver left and right automatically.
(Remote controller)
3rd : Repress the Airflow Direction Control Button to set the louver as the desired position.
(Remote controller)
8HP Model don't have this function.
3. Cooling Mode Operation
When selecting the Cooling(
controller and the operation diagram is as following.
Intake Air temp.
Setting Temp. +1°C
(Compressor ON)
Setting Temp. -1°C
(Compressor OFF)
Indoor Fan Speed
Compressor
) Mode Operation, the unit will operate according to the setting by the
More than
3 minutes
Selecting
Selecting
fan speed
fan speed
ON
OFF
Selecting
fan speed
ON
–9–
More than
3 minutes
Selecting
Selecting
fan speed
fan speed
OFF
ON

Advertisement

Table of Contents
loading

Table of Contents