Fujitsu AS*A09LKC Service Instructions Manual page 58

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for AS*A09LKC:
Table of Contents

Advertisement

2-2 Heating operation
Model Name : AS*A09 / 12LKC
[Condition]
Ambient
I Indoor / Outdoor - Same temperature
temperature
Refrigerant
Standard amount
amount
Piping
5.0m (Height difference 1m)
length
Power
50Hz - 230V
voltage
Operation
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
condition
Measure the high pressure with the pressure meter at the service valve.
Measuring
method
Measure the outdoor unit overall current with the current clamp meter at Power Cable.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*A09LKC
3.0
15 degC
20 degC (Indoor ambient temp.)
23 degC
2.8
2.6
2.4
2.2
2.0
0
2
4
Outdoor ambient temparature [degC]
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*A09LKC
5.8
15 degC
20 degC (Indoor ambient temp.)
23 degC
5.4
5.0
4.6
4.2
3.8
0
2
4
Outdoor ambient temparature [degC]
[50Hz-230V]
6
8
10
12
[50Hz-230V]
6
8
10
12
AS*A12LKC
3.8
15 degC
20 degC (Indoor ambient temp.)
23 degC
3.6
3.4
3.2
3.0
2.8
2.6
0
2
14
AS*A12LKC
7.6
15 degC
20 degC (Indoor ambient temp.)
23 degC
7.2
6.8
6.4
6.0
5.6
14
0
2
Outdoor ambient temparature [degC]
03-03
4
6
8
10
Outdoor ambient temparature [degC]
4
6
8
10
[50Hz-230V]
12
14
[50Hz-230V]
12
14