Fujitsu AS*A09LKC Service Instructions Manual page 36

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for AS*A09LKC:
Table of Contents

Advertisement

Trouble shooting 12
OUTDOOR UNIT Error Method:
CT Error
Detective Actuators:
Outdoor Unit Inverter PCB
Forecast of Cause :
1. Connection failure
Check Point 1-1 : Reset power supply and operate
Does error indication reappear?
YES
Check Point 2 :
Check connections condition in control unit
Check if the terminal connection is loose.
Check if connector is removed.
Check if connector is erroneous connection.
Check if cable is open.
>> Upon correcting the removed connector or mis-wiring,
reset the power.
OK
Check Point 3 : Replace Inverter PCB
If Check Point 1 ~ 2 do not improve the symptom,
Inverter PCB
replace
.
Indicate or Display:
Refer to error code table.
Detective details:
After compressor runs for 1 minute or more, and while it runs
in 56Hz or more.
When outdoor current value (A/D data) of Input Current Sensor
has detected [00H].
2. External cause
3. Inverter PCB failure
NO
02-14
Check Point 1-2 : Check external cause such as noise
Check if the ground connection is proper.
Check if there is any equipment that causes harmonic wave
near the power cable (Neon light bulb or any electronic
equipment which causes harmonic wave).