Fujitsu AS*A09LKC Service Instructions Manual page 27

Split type room air conditioner wall mounted type inverter
Hide thumbs Also See for AS*A09LKC:
Table of Contents

Advertisement

Trouble shooting 3
INDOOR UNIT Error Method:
Wired Remote Controller Error
Detective Actuators:
Indoor unit Controller PCB
Wired Remote Controller(Option)
Forecast of Cause:
1. Connection failure
Check Point 1 : Check the connection of terminal
Check & correct the followings.
Check the connection of terminal between Wired Remote Controller and indoor unit,
and check if there is a disconnection of the cable.
OK
OK
Check Point 2 : Check Wired Remote Controller and Controller PCB
Check voltage at connector of Wired Remote Controller of Controller PCB. (Power supply to Wired Remote Controller)
>> CN8, 1 - 3 pin
If it is DC12V, Wired Remote Controller is failure. (Controller PCB is normal)
>> Replace Wired Remote Controller (Option)
If it is DC 0V, Controller PCB is failure.
>> Replace Controller PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When the indoor unit cannot properly receive the signal from
Wired Remote Controller for 1 minute or more.
2. Wired Remote Controller failure
3. Controller PCB failure
02-05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

As*a12lkcAo*r12lkcAo*r09lkc

Table of Contents