Trouble shooting 8
OUTDOOR UNIT Error Method:
Outdoor Temperature Thermistor Error
Detective Actuators:
Outdoor Unit Inverter PCB
Outdoor Temperature Thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of connector
Check if connector is removed.
Check if connector is erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check thermistor resistance value
Thermistor characteristics (Approx. value)
Temperature
(°C )
Resistance value (k )
Temperature
(°C )
Resistance value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
AO*R09LKC
BLACK
1
1
BLACK
2
2
BLACK
3
3
BLACK
4
4
BLACK
1
1
2
2
BLACK
3
3
If the voltage does not appear, replace
Indicate or Display:
Refer to error code table.
Detective details:
When Outdoor Temperature Thermistor open or short-circuit
is detected at power ON or while running the compressor.
2. Thermistor failure
-20
-10
-5
115
62.3
46.6
30
40
50
7.97
5.18
3.45
THERMISTOR
( HEAT EXCHANGER )
THERMISTOR
( DISCHARGE PIPE )
THERMISTOR
( OUTDOOR TEMP. )
Inverter PCB
3. Inverter PCB failure
0
5
10
15
35.2
26.9
20.7
16.1
60
70
2.36
1.65
AO*R12LKC
BLACK
1
1
BLACK
2
2
BLACK
3
3
BLACK
4
4
BLACK
1
1
2
2
BLACK
3
3
.
02-10
20
12.6
THERMISTOR
( HEAT EXCHANGER )
THERMISTOR
( DISCHARGE PIPE )
THERMISTOR
( OUTDOOR TEMP. )