Section 23
Basic IED functions
23.2.2
23.3
608
Factory defined settings
The factory defined settings are very useful for identifying a specific version and very
helpful in the case of maintenance, repair, interchanging IEDs between different
Substation Automation Systems and upgrading. The factory made settings can not be
changed by the customer. They can only be viewed. The settings are found in the local
HMI under Main menu/Diagnostics/IED status/Product identifiers
The following identifiers are available:
•
IEDProdType
•
Describes the type of the IED. Example: REL670
•
ProductDef
•
Describes the release number from the production. Example: 2.1.0
•
FirmwareVer
•
Describes the firmware version.
•
The firmware version can be checked from Main menu/Diagnostics/IED
status/Product identifiers
•
Firmware version numbers run independently from the release production
numbers. For every release number there can be one or more firmware
versions depending on the small issues corrected in between releases.
•
ProductVer
•
Describes the product version. Example: 2.1.0
1 is the Major version of the manufactured product this means, new platform of the product
2 is the Minor version of the manufactured product this means, new functions or new
hardware added to the product
3 is the Major revision of the manufactured product this means, functions or hardware is
either changed or enhanced in the product
•
IEDMainFunType
•
Main function type code according to IEC 60870-5-103. Example: 128
(meaning line protection).
•
SerialNo
•
OrderingNo
•
ProductionDate
Measured value expander block RANGE_XP
1MRK 511 401-UUS A
M11789-39 v10
SEMOD52451-1 v2
Bay control REC670 2.2 ANSI
Application manual