Section 14
Control
14.2.2.14
332
Table 32:
Type of reclosing shots at different settings of ARMode or integer inputs to MODEINT
MODEINT (integer)
1
2
3
4
1ph + 1*2ph
5
1/2ph + 1*3ph
6
1ph + 1*2/3ph
A start of a new auto reclosing cycle during the set "reset time" is blocked when the set
number of reclosing shots have been reached.

External selection of auto reclosing mode

The auto reclosing mode can be selected by use of available logic function blocks.
Below is an example where the choice of mode, ARMode=3ph or ARMode=1/2/3ph, is
done from a hardware function key at the front of the IED, but alternatively there can
for example, be a physical selector switch on the front of the panel which is connected
to a binary to integer function block (BTIGAPC).
The connection example for selection of the auto reclosing mode is shown in Figure
114.
ARMode
Type of fault
1ph
3ph
2ph
3ph
1ph
1/2/3ph
2ph
3ph
1ph
1/2ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
1ph
2ph
3ph
1MRK 511 401-UUS A
1st shot
2nd-5th shot
3ph
3ph
3ph
3ph
3ph
3ph
1ph
3ph
2ph
3ph
3ph
3ph
1ph
3ph
2ph
3ph
.....
.....
1ph
3ph
2ph
.....
.....
.....
1ph
3ph
2ph
3ph
3ph
.....
1ph
3ph
2ph
.....
3ph
.....
M12391-241 v5
Bay control REC670 2.2 ANSI
Application manual