Interlocking For Bus-Section Breaker A1A2_Bs (3) - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 14
Control
14.4.5
14.4.5.1
14.4.5.2
386
If there is no second busbar B at the other side of the transformer and therefore no 489
disconnector, then the state for 489 is set to open by setting the appropriate module
inputs as follows:
489_OP = 1
489_CL = 0

Interlocking for bus-section breaker A1A2_BS (3)

Application
The interlocking for bus-section breaker (A1A2_BS ,3) function is used for one bus-
section circuit breaker between section 1 and 2 according to figure 142. The function
can be used for different busbars, which includes a bus-section circuit breaker.
WA1 (A1)
189G
ANSI04000516 V1 EN-US
Figure 142:
Switchyard layout A1A2_BS (3)
The signals from other bays connected to the module A1A2_BS are described below.
Signals from all feeders
If the busbar is divided by bus-section circuit breakers into bus-sections and both
circuit breakers are closed, the opening of the circuit breaker must be blocked if a bus-
coupler connection exists between busbars on one bus-section side and if on the other
bus-section side a busbar transfer is in progress:
WA2 (A2)
189
289
152
489G
389G
A1A2_BS
1MRK 511 401-UUS A
289G
en04000516_ansi.vsd
Bay control REC670 2.2 ANSI
Application manual
IP14154-1 v2
M15110-3 v7
M15111-4 v3
M15111-6 v4