Programming - basics
4.
5.
6.
7.
8.
34
Use the arrow keys to change the setting. Press ENTER to save.
The screen displays the HOLD prompt.
Use the arrow keys to change the setting to the output desired when the transmitter
is in hold mode.
The range is 3.80 to 22.0 mA. If 00.00 is selected, the transmitter will hold the
output value.
Press ENTER to save.
NOTICE
The hold setting overrides the fault setting.
The screen displays the FAULT prompt.
Use the arrow keys to change the setting to the output desired when the transmitter
is in fault mode.
The range is 3.80 to 22.0 mA. If 00.00 is selected, the transmitter will hold the
output value.
Press ENTER to save.
The screen displays the DPN prompt.
Rosemount 5081