4 Mounting

4.1 General instructions

Make sure that all parts of the instrument exposed to the process, in
particular the sensor element, process seal and process fitting, are
suitable for the existing process conditions. These include above all
the process pressure, process temperature as well as the chemical
properties of the medium.
You can find the specifications in chapter "Technical data" or on the
type label.
Lateral movements of the transmitter can cause measurement errors.
For this reason, mount the instrument in a calm area or in a suitable
protective tube.
The connection cable has a capillary for atmospheric pressure
compensation. Therefore lead the cable end into a dry environment or
a suitable terminal housing, for example VEGABOX 02 or VEGA-
DIS 62.
Fig. 3: Mounting example: VEGAWELL 52 in a pump shaft with breather housing
VEGABOX 02
4 Mounting
11