Omron NX-ILM400 User Manual page 150

Machine automation controller nx-series io-link master unit
Hide thumbs Also See for NX-ILM400:
Table of Contents

Advertisement

Appendices
Index
Subindex
(hex)
(hex)
5003
---
Restoration Settings
00
Number of Entries
01
Port 1 Restoration Setting
02
Port 2 Restoration Setting
03
Port 3 Restoration Setting
04
Port 4 Restoration Setting
*1. The meanings of the set values for the Restoration Settings are as follows:
Set value
00 hex
Restoration is disabled.
01 hex
Restoration is enabled.
Index
Subindex
(hex)
(hex)
5004
---
Load Rejection Output Settings ---
00
Number of Entries
01
Port 1 Load Rejection Output
Setting
02
Port 2 Load Rejection Output
Setting
03
Port 3 Load Rejection Output
Setting
04
Port 4 Load Rejection Output
Setting
*1. The Load Rejection Output Settings are used to set the load rejection outputs to use when controller communications
errors occur. The meanings of the set values are as follows:
Set value
00 hex
IO-Link Mode
Enabled: Output rejection notification is sent to the IO-Link device.
SIO (DO) Mode
Enabled: The output value is cleared to OFF.
01 hex
IO-Link Mode
Disabled: IO-Link communications continue with the last output data that was received.
SIO (DO) Mode
Disabled: The output that was last received is retained.
A - 24
Default
Object name
value
---
04 hex
00 hex
00 hex
00 hex
00 hex
Meaning
Default
Object name
value
04 hex
00 hex
00 hex
00 hex
00 hex
Data
Data range
Unit
type
---
---
04 hex
---
USINT
*1
---
USINT
00 or 01 hex
---
USINT
*1
00 or 01 hex
*1
---
USINT
00 or 01 hex
---
USINT
*1
00 or 01 hex
Data
Data range
Unit
type
---
---
04 hex
---
USINT
---
USINT
*1
00 or 01 hex
*1
---
USINT
00 or 01 hex
---
USINT
*1
00 or 01 hex
---
USINT
*1
00 or 01 hex
Meaning
NX-series IO-Link Master Unit User's Manual (W567)
I/O allo-
Data
Access
cation
attribute
---
---
RO
Not pos-
---
sible
RW
Not pos-
Y
sible
RW
Not pos-
Y
sible
RW
Not pos-
Y
sible
RW
Not pos-
Y
sible
I/O allo-
Data
Access
cation
attribute
---
---
RO
Not pos-
---
sible
RW
Not pos-
Y
sible
RW
Not pos-
Y
sible
RW
Not pos-
Y
sible
RW
Not pos-
Y
sible

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx-tba162

Table of Contents