Parameters

4.2 Module/channel parameters

4.2
Module/channel parameters
Parameters of the AI 16xTC/8xRTD 2-/3-/4-wire HA
You have the following setting options:
Table 4-1
Adjustable parameters and their default setting
Parameter
Value range
Diagnostics,
● Enabled
Missing supply volt‐
● Disabled
age L+
IO redundancy
● None
● 2 modules
Diagnostics
● Enabled
reference junction
● Disabled
Diagnostics overflow
● Enabled
● Disabled
Diagnostics
● Enabled
underflow
● Disabled
Diagnostics
● Enabled
wire break
● Disabled
Measurement type
● Disabled
● Voltage
● Resistor (2-, 3-, 4-wire connection)
● Thermal resistance (2-, 3-, 4-wire
● Thermocouple
Measuring range
-
(for measurement
type: Disabled)
Measuring range
● ±50 mV
(for measurement
● ±80 mV
type: Voltage)
● ±250 mV
● ±1 V
Measuring range
● 150 Ω
(for measurement
● 300 Ω
type: Resistance)
● 600 Ω
● 3 kΩ
● 6 kΩ
● PTC (only for 2-wire connection)
16
connection)
Default
Enabled
None
Enabled
Enabled
Enabled
Enabled
Thermocouple
-
±80 mV
600 Ω
Analog input module AI 16xTC/8xRTD 2-/3-/4-wire HA (6DL1134-6JH00-0PH1)
Reparameter‐
Efficiency
ize in RUN
range
Yes
Module
Yes
Module
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Manual, 05/2017, A5E39408175-AA