Parameters
4.4 Measurement types and measuring ranges
4.4
Measurement types and measuring ranges
Measurement types and channels
The measurement types for resistance measurement (incl. PTC) and resistance thermal
measurement are only possible on Channels 8...15. If a measurement type with 3-wire or 4-
wire connection is configured for channel x (x = 8...15), then channel y (y = x-8) must be
disabled because it is used for the power supply for channel x.
Measurement types and measuring ranges
The following table describes the measuring range and the temperature coefficients you can
configure for each measurement type:
Table 4-4
Measurement types and measuring ranges
Measurement type
Disabled
Resistor (2-, 3-, 4-wire connection)
Resistor (2-wire connection)
Thermal resistor RTD
(3-wire connection)
Thermal resistor RTD
(2, 3, 4-wire connection)
Thermocouple (TC)
Voltage
The preset temperature coefficients are valid for Europe.
1
For sensors LG-Ni 1000 from Siemens Building Ltd (Landis & Stäfa).
2
24
Channel
Measuring range
0...15
–
8...15
150 Ω / 300 Ω / 600 Ω /
3 kΩ / 6 kΩ
8...15
PTC
8...15
Climatic / Standard
Cu 10
8...15
Climatic / Standard
Pt 100
Pt 200
Pt 500
Pt 1000
Climatic / Standard
Ni 100
Ni 120
Ni 200
Ni 500
Ni 1000
Climatic
/ Standard
2
LG-Ni 1000
0...15
Type E, N, J, K, L, S, R,
B, T, C, U, TXK (acc. to GOST)
0...15
±50 mV / ±80 mV /
±250 mV / ±1 V
Analog input module AI 16xTC/8xRTD 2-/3-/4-wire HA (6DL1134-6JH00-0PH1)
Temperature coefficient
–
–
–
Cu 0.00427
Pt 0.00385 /
Pt 0.003916 /
Pt 0.003902 /
Pt 0.00392 /
Pt 0.00385055
Ni 0.00618 /
Ni 0.00672
LG-Ni 0.005
2
Manual, 05/2017, A5E39408175-AA