Drivers, parameters, diagnostics messages and address space

A.6 Address space

A.6

Address space

Abbreviations
● "IB" stands for input byte, that is, the module start address in the input area
● "QAIn" stands for value status (QI) of analog input n
Evaluating the value status
One bit value status each exists for each analog input in the input address space.
Irrespective of the diagnostics enables, each value status (each QI bit) provides information
on the validity of the corresponding process value.
● Value status = 1: Process value okay, "good"
● Value status = 0: Process value not okay, "bad"
Basically, the value status is set to "good" when the analog value can be acquired without
error. The value status is set to "bad" in the following cases:
● The analog value cannot be acquired to a fault or error.
● The analog input is disabled.
Address space
The following tables show the allocation of the address space of the AI 16xTC/8xRTD 2-/3-/4-
wire HA.
Input area
IB x +
0...1
:
:
30...31
32
33
58
7
6
5
Analog value, analog input 0
Analog value analog input 15
QAI7
QAI6
QAI5
QAI15
QAI14
QAI13
Analog input module AI 16xTC/8xRTD 2-/3-/4-wire HA (6DL1134-6JH00-0PH1)
4
3
2
QAI4
QAI3
QAI2
QAI12
QAI11
QAI10
Manual, 05/2017, A5E39408175-AA
1
0
QAI1
QAI0
QAI9
QAI8