Parameters

4.2 Module/channel parameters

4.2
Module/channel parameters
Parameters of the DI 8x24...125VDC HA
You have the following setting options:
Table 4-1
Parameters and their default settings
Parameters
Diagnostics,
Missing supply voltage L+
Diagnostics
Wire break
1
Wire break
check
2
Operating mode
Input delay
3
Hardware interrupts positive
edge
3
Hardware interrupts nega‐
tive edge
3
Potential group
The wire break diagnostics can only be enabled when the "Check for wire break" parameter is enabled.
1
If you use simple encoder contacts, you need to connect a resistor in parallel to enable a wire break check to be performed
2
when the contacts are open. The resistor used depends on the nominal input voltage of the module (see table 2-2).
When time stamping with an accuracy of 1 ms is enabled, the input delay on all channels is switched off and the pulse
3
stretching and hardware interrupt for positive/negative edge is disabled on all channels (not adjustable).
Parameter reassignment
Each configuration change resets the corresponding reaction.
14
Value range
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● None
● 0.05 ms
● 0.1 ms
● 0.4 ms
● 0.8 ms
● 1.6 ms
● 3.2 ms
● 12.8 ms
● 20 ms
● Enabled
● Disabled
● Enabled
● Disabled
● Use potential group of the left
module
● Allow new potential group
[ID: 91143428107]
Default
Enabled
Enabled
Enabled
Enabled
3.2 ms
Disabled
Disabled
Use potential
group of the left
module
Digital input module DI 8x24...125VDC HA (6DL1131-6DF00-0PK0)
Parameter re‐
Efficiency range
assignment in
RUN
Yes
Module
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
Yes
Channel
No
Module
Manual, 11/2017, A5E39288633-AB