Maintenance

9.1

Maintenance and servicing

For your personal safety and in order to prevent material damage it is essential that you follow
the instructions given in section "Safety instructions" (Page 13), especially section "Information
about personal protection" (Page 16), and all safety-related instructions in your product
documentation. Pay particular attention to the safety notices on the product itself.
There is an appropriate maintenance schedule for each device type. We recommended that
maintenance is carried out at least once per year. For further information, please contact the
Service Center, see "Service & Support" (Page 161).
Retighten all screw connections at regular intervals.
Depending on utilization, the installed fans each have a service life of between 5 and 10 years.
The service life of the lithium battery on the board CB08 is 10 years.
The electrolyte capacitors are designed for a service life of 20 years.
● Service the device after 5 years in accordance with a specified maintenance schedule.
● Check and clean the equipment and air filter mats (if present) depending on the
Installation and operating instructions Sinamics G180
Operating Instructions, 05/2013, 4BS0751-001
accumulation of dust.