Hobart 140GT17P Operation And Maintenance Manual With Illustrated Parts List page 101

6906 series engine-driven generator set
Table of Contents

Advertisement

TROUBLE, SYMPTOM
AND CONDITION
ENGINE AND CONTROLS (CONTINUED)
9. Engine is unsteady
(surges) under load
10. Engine has slow
response time
September 30/89 Revised
PROBABLE CAUSE
A. Fault in engine
B. Governor system
faulty or mis-
adjusted
(1) Loose or binding
governor linkage
(2) GAIN and STABIL-
ITY controls im-
properly adjusted
(3) Magnetic pickup
signal weak
A. Governor control unit
improperly adjusted
B. Actuator linkage
binding
C. Engine needs tune-up
Trouble Shooting Chart (Sheet 7 of 20)
Figure 4
TEST, CHECK, AND/OR
REMEDY
A. Before condemning the gover-
nor system for surging, make
certain the fault is not in
the engine. Make certain all
cylinders are firing properly.
B. Check and adjust as follows:
(1) Check linkage ball
joints and all connec-
tions for looseness or
binding. Be sure linkage
will move from idle
speed to full speed
without lost motion or
binding.
(2) Adjust GAIN and STABIL-
ITY controls on control
unit in accordance with
2-3; Para. 3, E, (3).
(3) Check and adjust pickup.
See 2-3, Para. 3, E, (2)
A. Adjust. See 2-3; Para. 3, E,
(3).
B. Inspect and repair as re-
quired.
C. Tune-up as required. Refer
OM-2029
3-1
Page 13