I/O Response Time
Reducing Response Time

6-4-5 One-to-one Link I/O Response Time

Induction sequence processing: 15 ms x (8 PCs – 8 PCs) = 0 ms
I/O refresh bits for Unit 0
I/O refresh bits for Unit 7
IORF(97) can be used in programming to shorten the I/O response time greater
than is possible by setting a high number of refresh bits. (Remember, increasing
the number of refresh bits set on the back-panel LED shortens response time,
but increases the cycle time of the PC.)
The following calculations for the maximum cycle time use the same example
System configuration as that used in 5–2 Response Times. In programming the
PCs for PC Link Units #0 and #7, IORF(97) is executed during every PC scan for
the PC Link Units. The basic equation for the maximum I/O response time is as
follows:
Response time = Input ON delay + [Cycle time of PC of Unit 0 x (Number of LR
transfer bits ÷ Number of I/O refresh bits ÷ 2)] + α + PC Link
polling time + Induction sequence processing time + {Cycle
time of PC of Unit 7 x [(Number of LR transfer bits ÷ Number of
I/O refresh bits ÷ 2) x 2 + 1]} + β + Output ON delay
If cycle time of PC of Unit 0 > PC Link polling time, α = cycle time of PC of Unit 0. If
cycle time of PC of Unit 0 < PC Link polling time, α = PC Link polling time.
If cycle time of PC of Unit 7 > PC Link polling time, β = cycle time of PC of Unit 7. If
cycle time of PC of Unit 7 < PC Link polling time, β = PC Link polling time.
The required data from the example System configuration is as follows:
Input ON delay
Output ON delay
Cycle time of PC of Unit 0
Cycle time of PC of Unit 7
Number of PC Link Units
Number of LR bits
Number of refresh bits for Unit 0
Number of refresh bits for Unit 7
PC Link polling time
Induction sequence processing time
Placing these values into the equation produces a maximum I/O response time
of 466.9 ms, approximately 200 ms shorter than when IORF is not used.
When two C200HSs are linked one-to-one, the I/O response time is the time re-
quired for an input executed at one of the C200HSs to be output to the other
C200HS by means of one-to-one link communications.
One-to-one link communications are carried out reciprocally between the mas-
ter and the slave. The respective transmission times are as shown below, de-
pending on the number of LR words used.
Number of words used
64 words (LR 00 to LR 63)
32 words (LR 00 to LR 31)
16 words (LR 00 to LR 15)
256
256
1.5 ms
15 ms
20 ms + 5.7 ms = 25.7
(5.7 ms required for IORF execution)
50 ms + 5.7 ms = 55.7
(5.7 ms required for IORF execution)
8
1,024
256
256
2.8 ms x 8 PCs + 10 ms = 32.4 ms
15 ms x (8 PCs – 8 PCs) = 0 ms
Transmission time
39 ms
20 ms
10 ms
Section 6-4
339