Figure 1.3C D48A, D48L, D60A, D60L Table 2.6 Blower Speed Voltage Chart; Figure 2.16 Troubleshooting Motor Start Command; Figure 2.17 Troubleshooting Speed Voltage - Bard D25A2PA Installation And Service Instructions Manual

Table of Contents

Advertisement

< 1Ω
???VDC
Model
Blower Only
D25A/D25L
D28A/D28L
D35A/D35L
Same as
D36A/D36L
Free Cooling
Mode
D42A/D42L
D48A/D48L
D60A/D60L
Manual 2100-643C
Page
40 of 59
FIGURE 2.16
Troubleshooting Motor Start Command
Motor Start Command: With the meter set to Continuity Beeper,
place the black (–) lead on Pin 5 and the red (+) lead on Pin 4 of
the female portion of the Molex-style plug connecting the motor
controller to the back of the wall-mount control cabinet. Meter
should audibly alert a closed-contact condition.
Note the plug-pin "flats" for proper orientation of the plug.
Female Plug
FIGURE 2.17
Troubleshooting Speed Voltage
Speed Voltage: With the meter set to VDC, place the black (–) lead
on Pin 5 and the red (+) lead on Pin 1 of the female portion of the
Molex-style plug connecting the motor controller to the back of the
wall-mount control cabinet. Nominal voltage should be 2.8VDC to
7VDC. Reference Table 2.6 for exact voltage.
Note the plug-pin "flats" for proper orientation of the plug.
Female Plug
TABLE 2.6
Blower Speed Voltage Chart
Free Cooling Mode
Free Cooling Mode
Below 40°F
(CFM/VDC
(CFM/VDC
Speed Voltage)
Speed Voltage)
1500/6.0
Cooling
(CFM/VDC
Speed Voltage)
900/2.0
900/2.0
800/2.8
1100/3.8
1100/3.0
1100/4.0
800/2.8
1100/3.8
950/3.1
1250/4.7
1100/3.8
1600/6.3
1100/3.8
1600/6.3
Electric Heat
1100/4.0
1800/7.0
1100/4.0
1800/7.0
1800/7.0
1800/7.0
1800/7.0

Advertisement

Table of Contents
loading

Table of Contents