9. You can use the "Remove" button to delete a certificate.
Note
The entry is deleted immediately and without further inquiry. If you want to again use a
deleted certificate, you need to import it again from a storage medium.
10. Confirm your entries with "OK".
The dialog closes.
The list of certificates on the HMI device is updated.
4.3.8

Enabling PROFINET

PROFINET services must be enabled on the HMI device in the following circumstances:
● The HMI device is connected to the controller over PROFINET.
● Function keys or buttons are configured as PROFINET IO direct keys in the project.
● The backlighting of the HMI device is to be controlled with PROFIenergy.
Note
If you enable PROFINET services, you cannot use the RS 422/RS 485 port as a serial
interface.
PROFINET IO direct keys and PROFIBUS DP direct keys are mutually exclusive.
Requirement
The Control Panel is open.
Procedure
1. Open the "Profinet" dialog using the "PROFINET" icon.
Comfort Panels
Operating Instructions, 07/2017, A5E36770603-AB
Enables or disables the PROFINET IO direct keys
Text box for the device name
MAC address of the HMI device
Commissioning the device
4.3 Parameter assignment for Comfort Panel
115