Field Setting And Monitor Mode List For Outdoor Unit - Fujitsu AUXB04GALH Service Manual

Airstage j-iiil series
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

1-4 FIELD SETTING AND MONITOR MODE LIST FOR OUTDOOR UNIT

Classification
Push switch on
Device and
system
outdoor unit PCB
Monitor mode
[ F1 ]
Operation of
each part
Time guard
Refrigerant
cycle data 1
Refrigerant
cycle data 2
Refrigerant
cycle data 3
Refrigerant
cycle data 4
ITEM
Setting Mode
CODE No.
00
Connected number of indoor unit
Software version of outdoor unit
01
02
Software version of INV PCB
03
Software version of communication PCB
10
Rotational speed of outdoor unit fan motor
11
Rotational speed of INV compressor
12
Current value of INV compressor
Forbidden
13
14
Pulse of EEV1
15
Pulse of EEV2
20
Accumulated current time
21
INV compressor accumulated time
[ Cooling ]
22
INV compressor accumulated time
[ Heating ]
Forbidden
23
Information on Thermistor 1
30
( INV compressor discharge temperature sensor )
Forbidden
31
32
Information on Thermistor 3
( Outdoor temperature sensor )
Information on Thermistor 4
33
( Suction temperature sensor )
34
Information on Thermistor 5
( Heat-exchanger (outlet) temperature sensor )
35
Forbidden
36
Information on Thermistor 7
( Liquid temperature sensor 2 )
37
Forbidden
Information on Thermistor 9
38
( Sub-cool heat-exchanger (outlet)
temperature sensor )
Information on Thermistor 10
39
( INV compressor temperature sensor )
40
Forbidden
Information on pressure sensor 1
50
( High pressure sensor )
Information on pressure sensor 2
51
( Low pressure sensor )
The number of the communicating unit is displayed
Software version :
[
] [
It skips when there is no suffix
The rotational speed of the outdoor unit fan motor is displayed
[ rpm ]
The rotational speed of the compressor is displayed
[ rps ]
Current value of INV compressor is displayed
[ A ]
Pulse of EEV1 is displayed
[ pls ]
Pulse of EEV2 is displayed
[ pls ]
Accumulated current time is displayed
[ 10 hour ]
Accumulated time is displayed in the cooling operation of the
INV compressor
[ 10 hour ]
Accumulated time is displayed in the heating operation of the
INV compressor
[ 10 hour ]
The value of the Thermistor 1 is displayed
[°C ] or
[°F ]
The value of the Thermistor 3 is displayed
[°C ] or
[°F ]
The value of the Thermistor 4 is displayed
[°C ] or
[°F ]
The value of the Thermistor 5 is displayed
[°C ] or
[°F ]
The value of the Thermistor 7 is displayed
[°C ] or
[°F ]
The value of the Thermistor 9 is displayed
[°C ] or
[°F ]
The value of the Thermistor 10 is displayed
[°C ] or
[°F ]
The value of the pressure sensor 1 is displayed
[ MPa ] or [ psi ]
The value of the pressure sensor 2 is displayed
[ MPa ] or [ psi ]
01-16
Information contents
] [
] [
] [
] displays by five items