Outdoor Temperature Protected Operation For Outdoor - Fujitsu AUXB04GALH Service Manual

Airstage j-iiil series
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

3-6-4 Outdoor temperature protected operation for Outdoor air unit
1. COOL OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
a) Operation mode management is made
"Management by indoor unit", and
outdoor air unit is master indoor unit.
Suction airflow
temperature rises
20°C
10°C
-5°C
Forced thermostat off
and Fan off
2. HEAT OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
Suction airflow
temperature rises
21°C
-5°C
Forced thermostat off
and Fan off
3. FAN OPERATION
The contents of operation is controlled as following based on the suction airflow temperature.
a) Operation mode management is made
"Management by indoor unit", and
outdoor air unit is master indoor unit.
Suction airflow
temperature rises
10°C
-5°C
Forced thermostat off
and Fan off
Suction airflow
temperature drops
Cooling operation
Fan operation
Heating operation
Suction airflow
temperature drops
Fan operation
Heating operation
Suction airflow
temperature drops
Fan operation
Heating operation
b) Cases Other than (a)
Suction airflow
temperature rises
20°C
18°C
10°C
5°C
-7°C
19°C
-7°C
b) Cases Other than (a)
Suction airflow
temperature rises
10°C
5°C
-7°C
03-16
Suction airflow
temperature drops
Cooling operation
Fan operation
Forced thermostat off
and Fan off
Suction airflow
temperature drops
Fan operation
Forced thermostat off
and Fan off
18°C
5°C
5°C