1-2-2 Check Items After Power ON

[Note]
Cooling test run for each refrigerant circuit.
If multiple refrigerant circuits are test run at the same time, refrigerant circuit address setting errors cannot be detected.
Procedure
Check contents
Outdoor unit circuit breaker ON
Power ON
Indoor unit circuit breaker ON
[Note] Turn on all indoor units power in the same refrigerant circuit address.
When the system operates with the indoor units remaining no power, it is cause of malfunction.
Outdoor unit Main
PCB push button
Function setting
SW setting/check
Automatic address setting
Address
setting/
Address read
check
Address record
Address hold check
Indoor unit
Indoor unit connection check
connection check
[Note] Before connecting service tool, the address setting has to be completed.
Outdoor unit push button
Cooling
SW operation
test run
<On service tool>
High pressure
Low pressure
Discharge pipe temperature (outdoor unit)
Suction pipe temperature (outdoor unit)
Inlet air temperature (indoor unit)
All of the
Heat exchange inlet temperature (indoor unit)
indoor units
Heat exchange outlet temperature (indoor unit)
operation
Compressor operation
(after 30 mins)
Data output
<Outdoor unit>
Outdoor Main PCB 7-seg. display
Operation voltage
Abnormal sound/
abnormal vibration
<Indoor unit service tool + actual measurement>
Outlet air temperature
Abnormal sound/abnormal vibration
Water leakage check
Remote controller operation
Check lighting of Main PCB LED101 and 7-segment display.
Check whether or not indoor unit OPERATION and TIMER lamps flash alternately.
Are the necessary functions set ?
< For the setting, Refer to the page 01-16
Addresses shall be assigned to all indoor units / Signal amps.
Check for unset or duplicated addresses.
< For the setting, Refer to the page 01-06, 07 >
All the indoor units and outdoor units of the same refrigerant circuit can be
checked on the service tool.
Enter the set addresses in the check sheet.
Check whether or not the address setting is held by the service tool
after indoor/outdoor circuit breakers were turned OFF to ON.
Are the number of connecting indoor units correct ?
Is the total capacity of indoor units correct ?
< For the checking, Refer to the page 01-08 >
All the indoor units in the same refrigerant circuit shall enter the cooling test run
state. The outdoor units corresponding to the operation capacity of the indoor
units shall operate.
< Test operation procedure, Refer to the page 01-09,10 >
HPS: 2.7 ~ 3.0 MPa
LPS: 0.9 ~ 1.0 MPa
TH1: 81°C
TH4: 15°C
TH21: 27°C
TH22: 11°C
TH24: 13°C
Shall operate corresponding to the operation capacity of the indoor units.
Service tool used, output (CSV
There shall be no Error information on the 7-segment display on the Main PCB.
3 Phase: 342 to 456V
These shall be no abnormal sound or abnormal vibration.
The outdoor fan shall not make a moaning sound.
There shall be no discharge air leaking from the outdoor duct.
There shall be no pipe chattering sound or flute sound generated.
Inlet air temperature and outlet air temperature difference shall be 10°C or
greater.
There shall be no abnormal sound or abnormal vibration.
There shall be no water leakage. There shall be no condensation on the drain,
cabinet, piping, and discharge port.
Shall operate according to the settings. (ON-OFF, set temperature change)
01-04
Judgement standard
19 >