Alternate Communicator Setup; Testing The System; Installer Walk Test; Assign Zone Types - DSC HS2032 Installation Manual

Power neo series alarm control
Hide thumbs Also See for HS2032:
Table of Contents

Advertisement

placed in common areas of the premises, such as points of entry or
reception areas, where the ability to arm and disarm more than one
partition at a time is required.
Partition keypads can also be temporarily loaned to other partitions.
To select a keypad operating mode:
1. Enter Installer Programming: [*][8][installer code].
2. Select [861]-[876] to program keypads 1-16.
Press [000] for partition assignment.
l
For Global operation, key in 00.
l
To assign a keypad to a partition, key in 01-08 for partition 1-8.
l
3. Press the [#] and reapeat step 2 for next keypad. When finished
programming all keypads, press the [#] key twice to exit
programming.
Users are assigned partition access rights via the [*][5] menu.
Assign sirens to partitions:
[804]>[000]>[551]-[556]>[000]
Set up partition account codes:
[310]>[001]-[008]
Set up partition timers:
Entry/exit delay, settle delay – [005]>[001]-[008]
l
Automatic arming/disarming schedule – [151]-[158]>[001]/[002]
l
Auto disarming holiday schedule – [151]-[158]>[003]
l
No activity arming – [151]-[158]>[006]
l
Automatic clock adjust – [005]>[000], option 6
l
Delay between dialing attempts – [377]>[012]
l

Assign Zone Types

A zone type defines how a zone operates within the system and how it
responds when triggered.
000 - Null Zone
001 - Delay 1
002 - Delay 2
003 - Instant
004 - Interior
005 - Interior Stay/Away
006 - Delay Stay/Away
007 - Delayed 24-Hour Fire
008 - Standard 24-Hour Fire
009 - Instant Stay/Away
010 - Interior Delay
011 - Day Zone
012 - Night Zone
016 - Final Door Set
017 - 24-Hour Burglary
018 - 24-Hour Bell/Buzzer
023 - 24-Hour Supervisory
024 - 24-Hour Supervisory Buzzer 069 - Maintained Keyswitch Disarm
025 - Auto Verified Fire
027 - Fire Supervisory
Assign zone attributes:
[002]>[001]-[128]>Select one of the following zone attributes:
1 – Bell Audible
2 – Bell Steady
3 – Chime Function
PowerSeries Neo Installation Guide
040 - 24-Hour Gas
041 - 24-Hour CO
042 - 24-Hour Holdup*
043 - 24-Hour Panic
045 - 24-Hour Heat
046 - 24-Hour Medical*
047 - 24-Hour Emergency
048 - 24-Hour Sprinkler*
049 - 24-Hour Flood
051 - 24-Hour Latching Tamper
052 - 24-Hour Non-Alarm
056 - 24-Hour High Temperature
057 - 24 Hour Low Temperature
060 - 24-Hour Non-Latching Tamper
066 - Momentary Keyswitch Arm
067 - Maintained Keyswitch Arm
068 - Momentary Keyswitch Disarm
071 - Door Bell
072 - Push to Set
* Not UL evaluated
4 – Bypass Enabled
5 – Force Arm
6 – Swinger Shutdown
7 – Transmission Delay
8 – Burglary Verification
9 – Normally Closed EOL
10 – Single EOL
11 – Double EOL
12 – Fast/Normal Loop Response
13 – Zone 2-way Audio Activation
14 – Hold Up Verification
Create labels:
[000]>[001]-[821] 2 x 14 ASCII characters.
Add access codes:
To program an access code: [006] then one of the following:
[001] – Installer code
[002] – Master code
[003] – Maintenance code
Access codes are either 4, 6 or 8 digits in length, depending on the setting
of programming section [041]. Duplicate codes are not valid.

Alternate Communicator Setup

The alternate communicator is an optional wireless or ethernet
communications device that can be used as a backup to the PSTN
connection or as a primary means of communication between the alarm
panel and the central monitoring station. The alternate communicator
communicates via 3G (HSPA) or Ethernet.
The following configuration steps are required to set up the alternate
communicator:
Install the alternate communicator and wire it to the alarm panel
l
(use PCLINK_2 header)
Enroll the alternate cellular communicator with Connect 24
l
Set the communication path: [300]
l
Enable the alternate communicator: [382] option 5
l
Enable event reporting: [307]/[308]
l
Program communication delay timer: [377]
l
Program DLS access: [401] option 07
l
Refer to the 3G2080(R)/ TL2803G(R)/ TL280(R) installation manual for
details.
[300] Panel/Receiver Communication Paths
This section is used to select the path of communications between the
alarm system and the central station.
To use PSTN as the communications path, program section [300] options
001 through 004 as [01] PSTN 1.
To use the alternate communicator to establish a communications path,
program two of the receivers (section [300] options 001, 002, 003 or 004)
as [03] and [04] for Ethernet, and two of the receivers as [05] and [06] for
cellular.

Testing the System

Installer Walk Test

Walk test enables the installer to test the operation of each detector by
tripping zones, causing an actual alarm. Enter section [901] to initiate a
walk test. When a zone is tripped, all system sirens emit a tone to indicate
that the zone is working correctly.