Double End of Line (DEOL) Resistors
When double end-of-line (DEOL) resistors are installed at the end of a
zone loop, the second resistor enables the panel to determine if the zone is
in open, closed, tampered or faulted.
Note: Any zone programmed for Fire or 24-hr Supervisory must be wired
with a SEOL resistor regardless of the type of zone wiring supervision
selected for the panel. If you change the zone supervision options from
DEOL to SEOL or from NC to DEOL, power the system down
completely, then power it back up for correct operation.
To enable DEOL supervision, program section [013], option [1] to OFF
and option [2] to ON.
Figure 1-4 DEOL Wiring

Bell Wiring

These terminals supply 700mA of current at 10.4 - 12.5VDC for
commercial/ residential installations. To comply with NFPA 72 Temporal
Three Pattern requirements, section [013] Opt [8] must be ON. Note that
steady, pulsed alarms are also supported.
Figure 1-5 Bell Wiring
The Bell output is supervised and power limited by 2A thermistor. If
unused, connect a 1000Ω resistor across Bell+ and Bell- to prevent the
panel from displaying a trouble.

Telephone Line Wiring

Wire the telephone connection terminals (TIP, Ring, T-1, R-1) to an RJ-
31x connector as indicated in the following diagram. For connection of
multiple devices to the telephone line, wire in the sequence indicated. Use
26 AWG wire minimum for wiring.
Figure 1-6 Telephone Line Wiring
Telephone format is programmed in option [350]. Telephone call
directions are programmed in options [311]- [318].
PowerSeries Neo Installation Guide
Ground Wiring
Figure 1-7 Ground Installation
Note: Using an insulated green wire (minimum 22AWG), connect the
EGND terminal on the Corbus and the grounding wire from the building
electrical installation to any of the available holes on the back or side of the
metal cabinet. See the diagram attached to the cabinet for suggested GND
point location and hardware recommendations.
Note: Wire and installation hardware not included.
Enrollment
All optional modules and devices must be enrolled on the system. During
enrollment, the electronic serial number (ESN) of each device is identified
to the control panel and zones are assigned. A wireless transceiver
HSM2HOST or an RF keypad must be enrolled first before wireless
devices can be enrolled.

Enrolling Modules

During automatic and manual enrollment, if an attempt is made to enroll
more than the maximum number of modules, an error tone sounds and a
message is displayed on LCD keypads.
Table 1-5 Module Capacity
Module
HSM2108 8 Zone expander
HSM2208 8 Output expander 2
Wireless Keypad:
HS2LCDRF(P)4
HS2ICNRF(P)4
HS2LCDWF(P)(V)4
HS2TCHP Touchscreen
Keypad
HSM2300 Power Supply 1A 3
HSM2204 4 High-current
Output
HSM2HOSTx Transceiver
HSM2955
Modules can be enrolled automatically or manually using section [902] of
Installer programming.
- 5 -
HS2016 HS2032 HS2064/
HS2064 E
1
3
7
4
8
8
8
8
8
8
8
3
3
1
1
3
1
1
1
1
1
1
HS2128/HS2128 E
15
16
16
16
4
4
1
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents