Panasonic FP3 Technical Manual page 61

Hide thumbs Also See for FP3:
Table of Contents

Advertisement

J To terminate the I/O control of the MEWNET- TR system
Set system register 21 to K1 (continue) and the operation mode selector No. 2 to the OFF position.
The COM. LED of the FP3 transmitter master unit flashes slowly when a communication error occurs.
To resume the operation, turn OFF the power supply of the master station. Then, after the cause of the communication
error is removed, turn the power supply ON.
1
2
3
MODE
4
SW.
5
6
7
8
ON
Operation mode selector of
FP3 transmitter master unit
J To continue the I/O control of the properly operating slave stations
Set system register 21 to K1 (continue) and the operation mode selector No. 2 to the ON position.
The I/O control continues for the slave stations that are properly connected when a communication error occurs.
When the cause of the communication error is removed, the I/O control resumes for the slave stations for which the
communication error occurred.
To cancel the error status, turn OFF the power supply of the master station.
1
2
3
MODE
4
SW.
5
6
7
8
ON
Operation mode selector of
FP3 transmitter master unit
Note:
See the "FP3/FP10S HARDWARE Technical Manual" and "FP3/FP5 Programming Manual" for details
about system register settings.
OFF
OFF
ON
OFF
4-1. Operation Mode Setting