F
IELD SETTING
Setting external static pressure
Depending on the external static pressure (ducts, filter, etc.) which is
connected to the air conditioning unit the fan speed should be set by
changing the wires in the switch box. (Refer to
Factory set:
fan speed is M.
High ESP:
fan speed is H.
Low ESP:
fan speed is L.
Setting air filter sign
Remote controllers are equipped with liquid crystal display air
filter signs to display the time to clean air filters.
Change the SECOND CODE No. according to the table
depending on the amount of dirt or dust in the room. (SECOND
CODE No. is factory set to "01" for filter contamination-light.)
Spacing time of
display air filter sign
Setting
(long life type)
Air filter contamination-light
±2500 hrs
Air filter contamination-heavy
±1250 hrs
Setting the remote sensor
The customer has the ability to select the thermistor. Both unit and
remote controller are equipped with a thermistor.
Setting
Setting
Mode n°
Enabled
20
Disabled
20
Change the second code n° according to the table to enable or
disable the remote sensor.
T
EST OPERATION
Refer to
"Check list" on page
After finishing the construction of refrigerant piping, drain piping, and
electric wiring, conduct test operation accordingly to protect the unit.
1.
Open the gas side stop valve.
2.
Open the liquid side stop valve.
3.
Electrify crank case heater for 6 hours.
4.
Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.
5.
Press Inspection/Test Operation button 4 times and operate at
Test Operation mode for 3 minutes.
6.
Press Inspection/Test Operation button and operate normally.
7.
Confirm function of unit according to the operation manual.
Precautions
In case something is wrong with the unit and it does not operate, refer
to the malfunction diagnosis label attached to the unit.
FDY(P)125~250B7V1 + FDQ125B7V3B
Split System air conditioners
4PW10621-1C
figure
5)
FIRST
Mode No.
CODE No.
10 (20)
0
1st code n°
2nd code n°
2
2
1.
NOTES
SECOND
CODE No.
01
02
01
02
Installation manual
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents