MINIMUM CLEARANCE TO COMBUSTIBLES

Minimum clearance to combustible construction from appliance and vent surfaces:
A
-
B
-
C
-
Combustible Framing:
-
-
NOTE: Appliance should not be installed directly on
carpeting.
Rear Exit:
-
Top Exit:
-
* HORIZONTAL VENT SECTIONS:
A minimum clearance of 1" (25mm) at the bottom and sides and 2" (51mm) at the top of the vent pipe in all
horizontal runs to combustibles is required. Use firestop spacer W010-1313 and shield W585-0267 (supplied).
* VERTICAL VENT SECTIONS:
A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is required. Use firestop
spacer W010-1313 (supplied).
** For top vent vertical termination, see "REAR EXIT" for specific clearances.
At a distance of 2" (51mm) from the wall, installation or service to the blower may not be practical. A minimum
of 5" (127mm) will be required in order to install or service the blower.
2" (51mm)
5" (127mm)
2" (51mm)
1" (25mm) to bottom and sides of the vent pipe*
2" (51mm) to top of the vent pipe*
47 1/2" (120.7cm) to ceiling from base of the appliance
51" (129.5cm) to ceiling from base of the appliance**
29
EN
BACK WALL
BACK WALL
W415-2183 / B / 02.10.17