Configuring The Switch Temperature Alarms; Setting A Secondary Temperature Threshold For The Switch - Cisco Catalyst 2950 Software Configuration Manual

Hide thumbs Also See for Catalyst 2950:
Table of Contents

Advertisement

Configuring Catalyst 2955 Switch Alarms
To disable sending the alarm to a relay, to syslog, or to an SNMP server, use the no alarm facility
power-supply relay, no alarm facility power-supply notifies, or no alarm facility power-supply
syslog global configuration commands.
Before you can use the notifies command to send alarm traps to an SNMP server, you must first set up
Note
the SNMP server by using the snmp-server enable traps alarms global configuration command. See
the
This example sets the power-supply monitoring alarm to the minor relay.
Switch(config) # alarm facility power-supply relay minor

Configuring the Switch Temperature Alarms

The temperature thresholds for the primary temperature alarm cannot be changed, but you can change
the association of the primary temperature alarm from the major relay to the minor relay. You can also
set a lower maximum temperature threshold for the secondary temperature alarm and associate the alarm
with either the major or minor relay.
This section describes how to configure the temperature alarms on your switch. It contains this
configuration information:

Setting a Secondary Temperature Threshold for the Switch

In global configuration mode, you can use the alarm facility temperature secondary command to set
a lower temperature threshold for the secondary temperature monitoring alarm. You can also use the
alarm facility temperature secondary command to associate the secondary temperature alarm to either
the major or minor alarm relay.
Beginning in privileged EXEC mode, follow these steps to set a lower temperature threshold:
Command
Step 1
configure terminal
Step 2
alarm facility temperature
secondary threshold
Step 3
end
Step 4
show alarm settings
Step 5
copy running-config startup-config (Optional) Save your entries in the configuration file.
Use the no alarm facility temperature secondary threshold global configuration command to disable
the secondary temperature threshold alarm.
This example disables the secondary temperature alarm.
Switch(config) # no alarm facility temperature secondary 45
Catalyst 2950 and Catalyst 2955 Switch Software Configuration Guide
3-6
"Enabling SNMP Traps" section on page
Setting a Secondary Temperature Threshold for the Switch, page 3-6
Associating the Temperature Alarms to a Relay, page 3-7
Purpose
Enter global configuration mode.
Set the secondary temperature threshold value. Enter values from 40 to 95 to
set threshold from 40
Return to privileged EXEC mode.
Verify the configuration.
Chapter 3
Configuring Catalyst 2955 Switch Alarms
3-11.
o
o
C to 95
C.
78-11380-12