Bosch AVIOTEC IPSTARLIGHT 8000 Operation Manual page 6

Hide thumbs Also See for AVIOTEC IPSTARLIGHT 8000:
Table of Contents

Advertisement

6
en | Safety instructions
AVIOTEC IP starlight 8000
Notice!
Avoid obstructions in the field of view!
Covered fires cannot be detected correctly. An unobstructed view of the detection area is
necessary.
Notice!
Activating video-based fire detection sets camera settings to a specific preset.
This preset affects several camera settings as long as this mode is activated.
Notice!
No detection of moving fire.
Moving fires will not be detected by the video-based fire detection.
Notice!
Indoor use only.
This product is designed for indoor use only. Outdoor use is not allowed.
Notice!
No direct connection to fire services in EN54 compliant installations.
Authorities can allow a connection to fire services after verifying alarms in a monitoring
center.
Notice!
Minimum Illumination required.
To ensure the proper functioning of the video-based fire detection algorithm, a minimal
illumination of 7 lx is required.
Notice!
No existing standards.
There are no existing EN standards concerning the video-based fire detection.
Notice!
Calm wind conditions only.
Strong air currents can cause false alarms by raising dust or debris similar in appearance to
fire and smoke.
Notice!
Respect data protection.
The relevant data protection and privacy rules are to be complied with.
Notice!
Avoid backlight.
Backlight can disturb the video-based fire detection algorithm.
2017.06 | 6.0 | F.01U.318.200