Discharge Pipe Temperature Control - Daikin K-Series Service Manual

Floor standing
Table of Contents

Advertisement

SiBE061121.book Page 35 Monday, April 25, 2011 3:20 PM
SiBE061121
3.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep this temperature from going up further.
Detail
Function and Control
B˚C
C˚C
D˚C
Discharge pipe
temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
25/35 class
50 class
A (°C)
110
B (°C)
105
C (°C)
101
D (°C)
99
E (°C)
97
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
Control
110
103
101.5
100
95
Control Specification
A˚C
E˚C
(R14642)
35